F-CIM 64
SETPOINT GENERATOR - 2
NOT REUSABLE
NAME SYMBOL DATAPOINT
INPUTS
S
n-1
REMOTE SETPOINT RSP2 C192
A REMOTE SP ENABLE RE2 L163
B SETPOINT TRACK INPUT STV2 C200
C SETPOINT TRACK SWITCH SWSPT2 L164
PARAMETERS SETPOINT TRACK ENABLE STE2 L166
REMOTE GAIN K12 C185
REMOTE BIAS B12 C184
INSTRUMENT RANGE IR2 C187
SETPOINT HI LIMIT SH2 C197
SETPOINT LOW LIMIT SL2 C198
OUTPUTS
S
n
SETPOINT SP2 C173
SETPOINT TRACK STATUS SPTS2 L152
REMOTE STATUS RMT2 L156
REMOTE SWITCH SWR2 L161
Description:
This module selects one of three signals to load into SP and become its output
(S
n
). The signal selected is either the Setpoint Tracking Value (B), the Remote
Setpoint Value (S
n-1
) multiplied by K1 and biased by B1, or the Setpoint pushbut-
ton value. If the Setpoint Track Switch (C) is less than 1, then Sn=B when Set-
point Tracking is enabled (STE=1). When the previous condition is not in effect S
n
will equal S
n-1
x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the
R/L pushbutton has set Remote Switch to1. When none of the previous conditions
are in effect the selected signal comes directly from the setpoint increase and de-
crease pushbuttons.