2.7.31 SETPOINT GENERATOR 2
The Setpoint Generator 2 (SPG 2) module provides a continuous output signal that is derived from
one of three sources which are the setpoint track value (STV), the remote setpoint (RSP), or the lo-
cal setpoint push buttons. The output priority is STV, RSP, and setpoint push buttons. The input
variable parameter values also affect the output, as determined by the setpoint selection made.
The two tables that follow list the input variables and the parameters. As shown in the third table,
two logical output signals, L152 and L156, indicate which source is supplying the continuous out-
put signal at C173. An illustration of the SPG 2 module follows the tables.
Inputs Inputs
WIRELIST SYMBOL DATA
TYPE
ASSIGNED VALUE WIRELIST SYMBOL DATA
TYPE
ASSIGNED VALUE
B212 STV2 C B214 RSP2 C
B213 SWSPT2 L B215 RE2 L
Output Datapoints:
C173, L152, L156
Parameters Parameters
SYMBOL DATAPOINT ASSIGNED VALUE SYMBOL DATAPOINT ASSIGNED VALUE
IR2 C187 SH2 C197
STE2 L166 SL2 C198
K1-2 C185 SWR2 L161
B1-2 C184 SPM2 B348
L156 L152 C173 OUTPUT
0 0 Setpoint push button value.
1 0 Remote Value - RSP (when SWR = 1 and RE = 1, RMT is true - lower toggle to 1). RSP modified by
K1 and B1 out.
0 1 Setpoint Track Value - STV (when SWSPT = 0, and STE = 1, SPTS is true - upper toggle to 1). STV
out.
1 1 Setpoint Track Value - STV (same as above, but both toggles at 1).
B1-2...remote setpoint bias
IR2...controller span
K1-2...remote setpoint ratio
RE2...remote setpoint enable
R/L2...remote/local
RMT2...remote status
RSP2...remote setpoint
SH2...setpoint high value
SL2...setpoint low value
SP2...setpoint
SPM2...setpoint mode
SPTS2...setpoint track status
STE2...setpoint track enable
STV2...setpoint track value
SWR2...remote switch
SWSPT2...setpoint track switch
FCS 53MC5000 Flexible Control Strategies
2-44
SPG-2