Single Loop Process Controller Instruction Manual
28 Front Panel
3.3.1 Displaying a Datapoint
The following procedure illustrates how to enter EMODE and use the display function to access the con-
tents of datapoint A001 (A1). The displayed contents will be PERCENT. Figure 3-9 and Figure 3-10 are
supporting illustrations for the display procedure which is described in Table 3-2. It should be noted that
EMODE has a 20 second timeout if it is accessed and its functions (e.g., configure or display) are not used.
Table 3-2. Procedures to Display a Datapoint
Step Press
Shift
Result
Press to
Locate
Target
Char.
Result
1
MODE
Puts instrument in EMODE.
2
If DISPLAY does not appear, press F2.
3
F3
Displays entry line: POINT .
4
A
Puts A on entry line: POINT .A.
5
.A∆↑ 1
Shifts A and puts 1 on entry line: POINT .A1.
6
F3
Enters address to display datapoint contents.
The address and the contents are displayed as
follows: A1 PERCENT.
7
MODE
Returns instrument to operator mode.
Note:
= space
Figure 3-9. POINT.A1