Single Loop Process Controller Instruction Manual
46 Configuration Parameters
Table 4-5. Analog Output Module
Title Symbol
ANO0
Datapoint
Default Attribute
Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the displayed
percent out.
Analog Output
(Display Only)
ANO C000 0
The value in this datapoint represents the percent of
output to be generated by hardware (e.g., 100%
output = 20 mA).
0 - 20 mA
Output
OZBASE L472 0
When a 0, the percentage output generates a 4 - 20
mA signal. When set to 1, the percentage output
generates a 0 - 20 mA signal.
Calibrate Zero
COZ B267
This is the calibration zero adjustment. This
parameter is factory set and should not need
adjustment under normal operation. See Section 12
for adjustment.
Calibrate Span
COS C300
This is the calibration span adjustment. This
parameter Is factory set and should not need
adjustment under normal operation. See Section 12
for adjustment.
Tag Name
AOTAG A244 ANO0
It is an assignable 10 character name for the analog
output (ANO0).
Table 4-6. Contact Input Module
Title Symbol
ANO0
Datapoint
Default Attribute
Purpose: The primary purpose allows the action of the CCI to be reversed (normally a closed contact = 1,
but can be changed to = 0).
Contact Input
(Display Only)
CCI L000 0
When open, a 4 - 24 V dc input signal = 0 when INV = 0.
When open, a 4 - 24 V dc input signal = 1 when INV = 1.
When closed, a < 1 V dc input signal = 1 when INV = 0.
When closed, a < 1 V dc input signal = 0 when INV = 1.
Contact Input
Invert
IINV L264 0
As shown above, it reverses the action of the CCI
datapoint.
Tagname
CITAG A262 CCI0
It is an assignable 10 character name for the contact
control input.