MOD 30ML Training Manual Operation and Maintenance Training Labs for MOD 30ML Operation

Seite 2 - MicroMod Automation, Inc

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 8 1.4.7 Checking the Communication setup Objective: Determine the Modbus address and

Seite 3 - 1.3 Equipment Required

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 9 Communication Information: Modbus Address Baud Rate Stop bits Built-In

Seite 4 - 1.4 Instructions

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 10 Notes:

Seite 5 - UAK = Unacknowledged alarm

2 - 1 2 MOD 30ML Operation Lab 2 2.1 Foreword MOD 30ML can perform complex continuous control as well as discrete control. The Sequencer block in t

Seite 6 -  Note: Active Diagnostics

Training Manual MOD 30ML Operation Lab 2 2 - 2 Figure 2 .1. Batch Temperature Cycle During the heat stage of the batch cycle, a cascade temperat

Seite 7

Training Manual MOD 30ML Operation Lab 2 2 - 3 • Manual advance of sequence Initial Conditions: 1. Batch AUTO, OFF (Note: once the batch has

Seite 8

Training Manual MOD 30ML Operation Lab 2 2 - 4 2.3 Instructions 2.3.1 Download Reactor database from the memory module: Step Procedure Comments

Seite 9

Training Manual MOD 30ML Operation Lab 2 2 - 5 2.3.2 Scroll through the displays: Step Activity Look For 1 The first display as shown in the p

Seite 10

Training Manual MOD 30ML Operation Lab 2 2 - 6  You can display and manipulate on one instrument, all process and calculated values associated w

Seite 11

Training Manual MOD 30ML Operation Lab 2 2 - 7 2.3.4 Run the Batch: 5 Press the TAG key to return to main Batch display Press AUTO key to sta

Seite 12

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applic

Seite 13 - MOD 30ML Operation Lab 2

Training Manual MOD 30ML Operation Lab 2 2 - 8 7 Return to main batch display and observe step. 8 When controller has entered HEATUP step,

Seite 14 - Batch Reactor

Training Manual MOD 30ML Operation Lab 2 2 - 9 2.3.5 Switch the batch control modes: 9 When batch cycle has entered HOLD step, return to main b

Seite 15

Training Manual MOD 30ML Operation Lab 2 2 - 10 11 Scroll to TIC-100 display Temperature setpoint ramping down to cool setpoint 12 When ba

Seite 16 - 2.3 Instructions

3 - 1 3 Single Loop Template Lab 3.1 Foreword Many processes involve flow control loops, whether they are in the food, pharmaceutical, chemical, pu

Seite 17 - Displays

Training Manual Single Loop Template Lab 3 - 2 3.3 Instructions 3.3.1 Power up the controller 1. We will remove the memory module if any fr

Seite 18 - Recipe Tuning

Training Manual Single Loop Template Lab 3 - 3 Figure 3 .3. MOD 30ML Alarm CLeaRed Alarm • The next figure shows an active alarm. Figure 3 .4.

Seite 19 - 2.3.4 Run the Batch:

Training Manual Single Loop Template Lab 3 - 4 3.3.3 Front face Configuration Map: The front face configuration map shows an overview of the menu

Seite 20 - Temperature

Training Manual Single Loop Template Lab 3 - 5 3.3.4 Scroll through the top level front face menus: Step Procedure Comments 1 Press and hold TA

Seite 21 - Cool Down Step

Training Manual Single Loop Template Lab 3 - 6 4 Press ENT again to enter Configuration mode. You will be in DEV STAT menu mow. See the s

Seite 22 - Batch End

Training Manual Single Loop Template Lab 3 - 7 Figure 3 .7. 13 Acknowledge UNCONFIG alarm by pressing the ALARM key and the AUTO key. The Al

Seite 23 - Single Loop Template Lab

1 - 1 1 MOD 30ML Front Face Familiarization Lab 1.1 Foreword Many processes involve flow control loops, whether they are in the food, pharmaceutica

Seite 24 - 3.3 Instructions

Training Manual Single Loop Template Lab 3 - 8 Figure 3 .8. 18 Press NXT key, then press the UP key You are exiting the COMMAND section

Seite 25

Training Manual Single Loop Template Lab 3 - 9 3.3.6 System Compound – Load Defaults: 1 Press NXT until TEMPLATE is displayed on line 6. S

Seite 26

Training Manual Single Loop Template Lab 3 - 10 Figure 3 .10. 3.3.7 System Compound – Edit System Template: We will change the System tag n

Seite 27

Training Manual Single Loop Template Lab 3 - 11 Figure 3 .11. . 7 Press NXT to access System Scan Groups. Scan groups defined update interv

Seite 28

Training Manual Single Loop Template Lab 3 - 12 We will change the system tune and configuration passwords in this section. 1 Press DOWN TUNE PAS

Seite 29

Training Manual Single Loop Template Lab 3 - 13 Next, we will change some of the system alarm settings. 1 Press DOWN DIAGNSTC RATE is displa

Seite 30

Training Manual Single Loop Template Lab 3 - 14 9 Press NXT HIGH PRI BEEP is OFF. OFF = beeping is disabled ENABLE = beep on alarm 10 Press

Seite 31

Training Manual Single Loop Template Lab 3 - 15 3.3.8 Single Loop PID control template setup: When you loaded defaults, you automatically created

Seite 32

Training Manual Single Loop Template Lab 3 - 16 assigned. 11 Press the UP key, then ENT to change loop to Scan Group 2 Figure 3 .15.

Seite 33

Training Manual Single Loop Template Lab 3 - 17 3.3.9 Process Input Setup 1 Press NXT PROC INP will be displayed on line 2. We are entering the

Seite 34

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 2 2. 1 x Memory module (2010PZ10000A) marked FACEPLATE (and loaded with the FACEPLA

Seite 35

Training Manual Single Loop Template Lab 3 - 18 key to set the range at 200. Then press ENT Significant Digit to flash, indicating you can change

Seite 36

Training Manual Single Loop Template Lab 3 - 19 16 Press NXT HI QUAL is displayed on line 2. Result is set BAD if it goes above this value. High

Seite 37

Training Manual Single Loop Template Lab 3 - 20 3.3.10 SETPOINT Setup 1 Press DOWN to enter setpoint section. 2 Press NXT until SETPOIN

Seite 38

Training Manual Single Loop Template Lab 3 - 21 3.3.11 CONTROL Setup 1 Press DOWN to enter control section. This takes you down into the Contro

Seite 39 - 3.3.9 Process Input Setup

Training Manual Single Loop Template Lab 3 - 22 3 Press NXT until “GAIN” is displayed on line 1. Set Gain at 0.65. Then press ENT. 0.01 to 12

Seite 40

Training Manual Single Loop Template Lab 3 - 23 3.3.12 OUTPUT Setup 1 Press DOWN to enter output section 2 Leave the default value of BI1

Seite 41

Training Manual Single Loop Template Lab 3 - 24 Figure 3 .24. 8 Set limit to 100.0 and press ENT 9 Press NXT until Line 2 displays O

Seite 42 - 3.3.10 SETPOINT Setup

Training Manual Single Loop Template Lab 3 - 25 3.3.13 Install the edited template 1 Press UP CMP LIST FIC 100 is displayed on lines 1 and 2.

Seite 43 - 3.3.11 CONTROL Setup

Training Manual Single Loop Template Lab 3 - 26

Seite 44

4 - 1 4 MOD 30ML Diagnostics Lab 4.1 Foreword The MOD 30ML provides a comprehensive way of displaying active diagnostic information as well as a hi

Seite 45 - 3.3.12 OUTPUT Setup

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 3 1.4.2 Operating the alarm page and power-up sequence Step Procedure Comments 1.

Seite 46

Training Manual MOD 30ML Diagnostics Lab 4 - 2 4.4 Instructions 4.4.1 Event Viewer The System Event block stores diagnostics reported by the dat

Seite 47

Training Manual MOD 30ML Diagnostics Lab 4 - 3 page1 6 Press NXT to display the next event in the queue. Page 1 of the next event will be dis

Seite 48

Training Manual MOD 30ML Diagnostics Lab 4 - 4 4.3.2 To clear events form the event history: The controller can store up to a maximum of 1000 ev

Seite 49 - MOD 30ML Diagnostics Lab

Training Manual MOD 30ML Diagnostics Lab 4 - 5 2 Press DOWN key once. If PASSWORD is not displayed on line 2, go to step 5. Otherwise continue w

Seite 50 - 4.4 Instructions

Training Manual MOD 30ML Diagnostics Lab 4 - 6 6 Press the DOWN key once. CLR Q is displayed on line 2. 7 Press the UP arrow. YES will

Seite 51

Training Manual MOD 30ML Diagnostics Lab 4 - 7 4.5 Instrument Shutdown 4.5.1 Force a shutdown Step Procedure Comments 1 Make sure the SERV/RUN

Seite 52

Training Manual MOD 30ML Diagnostics Lab 4 - 8 7 Press the SCROLL key ONCE. The PID setpoint will be shown on line 6 and the text “SP” on line

Seite 53

Training Manual MOD 30ML Diagnostics Lab 4 - 9 4.5.2 Read the shutdown information and acknowledge it: Step Procedure Comments 1 The first st

Seite 54

Training Manual MOD 30ML Diagnostics Lab 4 - 10 3 Press the TAG button after viewing and acknowledging the alarms. The instrument will display

Seite 55 - 4.5.1 Force a shutdown

Training Manual MOD 30ML Diagnostics Lab 4 - 11 7 Press the NXT key to view Pages1, 2 3 and 4 and record the information Shutdown page 2 display

Seite 56

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 4  Note: Active Diagnostics An unacknowledged diagnostic condition is always indicat

Seite 57

Training Manual MOD 30ML Diagnostics Lab 4 - 12 Notes:

Seite 58

Front Face ConfigurationFront Face ConfigurationMapMapTouring The MOD 30ML Front Face Configuration Menus

Seite 59

This Page Left Intentionally Blank

Seite 60

NEXTDEV STAST SET UP I/O EVENTS ABOUT TEMPLATESee Page 2 See Page 3EVENTS *DEVICE**DEVICE* ANY TAGI/OBI AIN 1 AIN MABuilt in analog input 1S11

Seite 61 - Front Face Configuration

This Page Left Intentionally Blank

Seite 62

NEXTINSTATE COMMANDS XTIMESTIME DATE DAYCOMMANDS CLR MTClear Maximum timesCOMMANDS CLR QClear QueueDEV STAT COMMANDSCommandsRUNDEFAULTHOLDSHUT DOWNDEV

Seite 63 - A2_FrontFace_Config.ppt

This Page Left Intentionally Blank

Seite 64

From TEMPLATEINSTALL TEMPLATESYSTEM DEV TAGSystem device tagSYSTEM SCANGRPSSystem scan groupsSCAN GROUP 1Scan group 1 intervalSCAN GROUP 5Scan group 5

Seite 65 - From DEV STAT

This Page Left Intentionally Blank

Seite 66

From page 3 (EDIT user compound)NEXTTAG IDSTRINGSCAN GROUPCMP TYPE PROCESS I/P SETPOINTTAG ID STRINGLoop tag IDCTAG01 CMP TYPECompound typeCHANGE TYPE

Seite 67 - See Page 4

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 5 1.4.3 Operating the Loop display Left Bar will display the Process variable Middle

Seite 68

This Page Left Intentionally Blank

Seite 69

CONTROLOUTPUTALARMSCTAG01 CONTROLControlCONTROL ALGO TYPControl algorithm typeCONTROL ACTIONControl actionGAINRESETPREACTCONTROL FILTYPEFilter typeFIL

Seite 72

The Company’s policy is one of continuous product improvement and the right is reserved to modify the information

Seite 73

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 6 1.4.5 Operating the Ramp keys Objective: To manually set the control output to a va

Seite 74

Training Manual MOD 30ML Front Face Familiarization Lab 1 - 7 1.4.6 Operating the Scroll key Step Procedure Comments 1. Press the SCROLL key