MOD 30ML Functions
PROCESS ALARM DISPLAY BLOCK
2.6.2 Process Alarm Display Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 2-7. A description of each
attribute is provided in the attribute list that follows the table.
Table 2-7. Process Alarm Display Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name / Attribute Mnemonic Valid Values CWR Data Type Attr
Version VERSION 1, 2 – – R Long State 00
Block Length BLKLEN – – R Count 01
State
STATE RUN (0), HOLD (1), OFF (2),
DEBUG (3)
CWR Short State 02
Bad Inputs
BADINP REJECTED(0)
ACCEPTED(1),
CWR Discrete 03
Alarm Priority
PRIORITY 0 to 255 (0 = No
Unacknowledged Alarm)
CWR Long State 04
Alarm Activate Condition
(Trip Condition)
TRIPCOND LESS(0), LESS EQUAL(1),
GREATER (2), GREATER
EQUAL (3), EQUAL (4),
NOT EQUAL (5), or
DEVIATION (6)
CWR Short State 05
Suppress calculation?
SUPPRES
S
NO (0), YES (1) CWR Discrete 06
Unacknowledged U FALSE (0), TRUE (1) – WR Discrete 07
Unacknowledged Quality UQ GOOD (0), BAD (1) – WR Discrete 08
Alarm Active A FALSE (0), TRUE (1) – WR Discrete 09
Active Quality AQ GOOD (0), BAD (1) – WR Discrete 10
Report events?
REPORT NO (0), YES (1) CWR Discrete 11
Alarm Activate Value
(Trip Point)
TRIPVAL Local data for Floating-Point,
Count, Date, Msec Time,
Discrete, Short State, or
Long State data types.
CWR Same as
ALARMINP
12
Line 1 Text
TAG1 1-8 character ASCII string CWR ASCII 13
Line 2 Text
TAG2 1-8 character ASCII string CWR ASCII 14
Hi Range
HRNG Top of alarm input range CWR Same as
ALARMINP
15
Lo Range
LRNG Bottom of alarm input range CWR Same as
ALARMINP
16
Alarm Input
ALARMINP LSP or local data CWR Floating Pt,
Count, Date,
Msec Time,
Discrete,
Short State,
Long State,
17
Ack Input
ACKINP NONE or LSP C – R Discrete 18
Hysteresis
HYST 0.000000 to any positive
Floating Point Value
CWR Floating Pt 19
2-52