MOD 30ML Data Base Reference
BUILT-IN ANALOG OUTPUT BLOCK
2.8.2 Built-In Analog Output Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for
display and/or be used in making softwiring connections are listed in Table 2-11. A
description of each attribute is provided in the attribute list that follows the table.
Table 2-11. Built-In Analog Output Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name / Attribute Mnemonic Valid Values CWR Data Type Attr
Version VERSION – – R Long State 00
Block Length BLKLEN – – R Count 01
State STATE RUN (0) – – R Short State 02
Bad Inputs
BADINP Rejected (0), Accepted (1) CWR Discrete 03
Diagnostic Group
SUPPGRP NONE, 1 to 7 CWR Long State 04
I/O communications error
COMMERRS
ENABLE (0), SUPPRESS (1) CWR Discrete 05
Unacked I/O comm. error
COMMERR
U
NO (0), YES (1) – WR Discrete 06
Active I/O comm. error
COMMERRA
NO (0), YES (1) – – R Discrete 07
OUTPUT Error
OUTERRS ENABLE (0), SUPPRESS (1) CWR Discrete 08
Unacked Output error OUTERRU NO (0), YES (1) – WR Discrete 09
Active Output error OUTERRA NO (0), YES (1) – – R Discrete 10
Output Number
OUTNUM 1, 2 C – R Long State 11
Output Circuit Error ERROR – WR Short State 12
Mode
MODE MANUAL (0), AUTO (1) CWR Discrete 13
Action
ACTION REVERSE (0), DIRECT (1) CWR Discrete 14
Input Range, Top
INHI Floating Pt Value, E.U. CWR Floating Pt 15
Input Range, Bottom
INLO Floating Pt Value, E.U. CWR Floating Pt 16
Output Range, Top
OUTHI Floating Pt Value, Sig. Rng. CWR Floating Pt 17
Output Range, Bottom
OUTLO Floating Pt Value, Sig. Rng. CWR Floating Pt 18
Output to use on restart
RESTART PREVIOUS (0), PRESET (1) CWR Discrete 19
Output to use on failsafe
FSACT HOLD (0), PRESET (1) CWR Discrete 20
Restart preset value PRESET Floating Pt Value, E.U. CWR Floating Pt 21
Track status TRKSTAT NO TRACK (0), TRACK (1) – WR Discrete 22
Track status data quality TRKQ GOOD (0), BAD (1) – WR Discrete 23
Initial Scaled Result
RSC Floating Pt Value, E.U. CWR Floating Pt 24
Maximum Output MAXOUT Floating Pt Value, E.U. – – R Floating Pt 26
Input
INPUT LSP or Floating Pt Value, E.U. CWR Floating Pt 40
Result
R Floating Pt Value, Sig. Rng. CWR Floating Pt 50
Result Quality RQ GOOD (0), BAD (1) – WR Discrete 51