MOD 30ML Operation
SETUP
2-12
Table 7. System Template Configuration (Cont’d)
Step Step Description Line 1 Line 2 Line 6 Entry Description
7C System Passwords (Entry)
moves down to Step 7C1
NXT, PRV change step
SYSTEM PASWORDS
The passwords set here will restrict
access to tuning and configuration
features.
7C1 Tune Passwords
changes number, ENT enters
NXT, PRV change step
TUNE PASSWORD 0
Enter a number required to access
tuning parameters.
7C2 Configure Passwords
changes number, ENT enters
NXT, PRV change step
CONFIG PASSWORD 0
Enter a number required to access
configuration parameters.
7C3 Access Timeout
changes number, ENT enters
NXT, PRV change step
ACCESS TIMEOUT 0
0-54 minutes; 0=infinite
The time in minutes that the tune
and configure access levels will
timeout and return to the operate
level after last keyboard activity.
7C4 System (Passwords Exit)
moves up to Step 7C
NXT, PRV change step
SYSTEM
7D System Alarms (Entry)
moves down to Step 7D1
NXT, PRV change step
SYSTEM ALARMS
Alarm indication rates apply to
light, display and beeper. Alarms
are: unacknowledged diagnostics,
high or low process and deviation
conditions, and input quality.
7D1 Diagnostic Flash/Beep Rate
change value, ENT enters
NXT, PRV change step
DIAGNSTC RATE FAST
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D2 Diagnostic Flash
change value, ENT enters
NXT, PRV change step
DIAGNSTC FLASH OFF
OFF = flashing is disabled
ENABLE = flash display (LED
always flashes for diagnostic)
7D3 Diagnostic Beep
change value
DIAGNSTC BEEP ENABLE
OFF = beeping is disabled
ENABLE = beep for diagnostic
7D4 Minimum Low Alarm Priority
change value, ENT enters
NXT, PRV change step
MINIMUM LOW PRI 100
All process alarms with priority >=
this value (2 - 255) are considered
LOW priority for display purposes.
7D5 High Priority Process Alarm Flash/
Beep Rate
change value, ENT enters
NXT, PRV change step
HIGH PRI RATE FAST
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D6 High Priority Process Alarm Flash
change value, ENT enters
NXT, PRV change step
HIGH PRI FLASH OFF
OFF = flashing is disabled
ENABLE = flash display on alarm
7D7 High Priority Process Alarm Beep
change value, ENT enters
NXT, PRV change step
HIGH PRI BEEP OFF
OFF = beeping is disabled
ENABLE = beep on alarm
7D8 Low Priority Process Alarm Flash/
Beep Rate
change value, ENT enters
NXT, PRV change step
LOW PRI RATE SLOW
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D9 Low Priority Process Alarm Flash
change value, ENT enters
NXT, PRV change step
LOW PRI FLASH OFF
OFF = flashing is disabled
ENABLE = flash display on alarm