OPERATION
3-30
5. Manually adjust control output to bring process variable to required value. Ramping the
output should be slow enough to allow the process to respond without overshooting the
required control point.
An alternate procedure in Step 5 is to bring the process variable up part way, to see that the
control application responds in a controllable manner, then switch to the automatic mode
early in the startup and bring the process variable up to the operating point under automatic
control by adjusting the set-point.