MOD 30ML Operation
SETUP
2-20
Table 8. User Compound Template Configuration (Cont’d)
Step Step Description Line 1 Line 2 Line 6 Entry Description
8G Output (Entry)
moves down to Step 8G1
NXT, PRV change step
CTAG01 OUTPUT
8G1 Output Slot Position
change value, ENT enters
NXT, PRV change step
OUTPUT SLOT OUT CH 1
NONE, OUT CH 1, OUT CH 2,
S01 to S11. Only available outputs
are listed.
8G2 Output Low Signal
change value, ENT enters
NXT, PRV change step
OUTPUT LO SIGNL 4.0
0% of the output range.
8G3 Output High Signal
change value, ENT enters
NXT, PRV change step
OUTPUT HI SIGNL 20.0
100% of the output range.
8G4 Output Display Format
change value, ENT enters
NXT, PRV change step
OUTPUT DISP FMT FLOAT 3
Float 0 = x, Float 1 = x.x
Float 2 = x.xx and so forth to
Float 6 = x.xxxxxx
8G5
Output Low Limit
change value, ENT enters
NXT, PRV change step
OUTPUT LO LIMIT -10.0
PID output limited to this number or
above.
8G6
Output High Limit
change value, ENT enters
NXT, PRV change step
OUTPUT HI LIMIT 110.0
PID output limited to this number or
below.
8G7 Output Restart Type
change value, ENT enters
NXT, PRV change step
RESTART TYPE PREVIOUS
PREVIOUS, PRESET
8G8 Output Initial Value
change value, ENT enters
NXT, PRV change step
OUTPUT INIT VAL 0.0
8G9 Output (Exit)
moves up to Step 8G
NXT, PRV change step
COMPOUND
8H Alarms (Entry)
moves down to Step 8H1
NXT, PRV change step
CTAG01 ALARMS
8H1 Process Value Alarms
PV ALARMS
8H1A Process Value Alarm 1 Type
change value, ENT enters
NXT, PRV change step
NXT goes to Alarm 2 from NONE
PV ALM 1 TYPE NONE
NONE,
HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).
8H1A1 Process Value Alarm 1 Trip Value
PV ALM 1 TRIP VAL 0.000
Value where input will cause alarm
to trip.
8H1A2 Process Value Alarm 1 Hysteresis
PV ALM 1 HYSTRSIS 2.000
Absolute offset to clear alarm.
8H1A3 Process Value Alarm 1 Priority
PV ALM 1 PRIORITY 1
0 to 255. 0 = suppress unack.
8H1A4 Process Value Alarm 1 Digital Output
PV ALM 1 DIG OUT NONE
NONE, S01 through S11
8H1B Process Value Alarm 2 Type
Same as Alarm 1
PV ALM 2 TYPE NONE
NONE, HIGHHIGH, HIGH, LOW,
LOW LOW
8H1C Process Value Alarm 3 Type
Same as Alarm 1
PV ALM 3 TYPE NONE
NONE, HIGHHIGH, HIGH, LOW,
LOW LOW
8H1D Process Value Alarm 4 Type
Same as Alarm 1
PV ALM 4 TYPE NONE
NONE, HIGHHIGH, HIGH, LOW,
LOW LOW
8H1E Process Value Alarms (Exit)
moves up to Step 8H1
NXT, PRV change step
ALARMS