Micromod RetroPAK: SLC Configuration Manual Bedienungsanleitung Seite 165

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 394
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 164
Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID with Remote SP
Auto Bias: Bias value of remote setpoint is automatically manipulated to balance
transitions to remote. Remote setpoint bias input must be NONE.
Auto Ratio: Ratio value of remote setpoint is automatically manipulated to balance
transitions to remote. Remote setpoint ratio input must be NONE.
Remote setpoint bias input (RSPBI): The remote setpoint bias input is added to the
remote setpoint input when the setpoint mode is REMOTE. This may be an external
connection or internal value.
Remote setpoint ratio input (RSPRI): The remote setpoint ratio input is multiplied
against the remote setpoint input when the setpoint mode is REMOTE. This may be an
external connection or internal value.
Notice that the only setpoint mode allowed is REMOTE:
Figure P4.16.
Process Variable
Hi Alarm
Dual PID with
Remote SP
P4- 19
Seitenansicht 164
1 2 ... 160 161 162 163 164 165 166 167 168 169 170 ... 393 394

Kommentare zu diesen Handbüchern

Keine Kommentare