Function Code 28 – Analog/Digital Output
GENERAL DESCRIPTION
This function can be used to send an output (analog, digital or any other data type
supported by the MOD 30ML or Modcell) over the peer-to-peer network ICN
(Instrument Communication Network) to any other member on the network.
UTILIZATION
The MOD 30ML/MODCELL compound FC28 uses an OC (Output Communication)
block to send an output over the ICN.
Figure 28 .1.
Function Code 20
EXPLANATION
ICN is a proprietary communication network used for peer-to-peer communication
between the MOD 30 instruments, MOD 30ML, Modcell and the LCP (Local Control
Panel). The ICN allows up to 16 addresses (in most cases 16 instruments) on the network.
Each instrument needs to have a unique address on the ICN (0 thru F). The ICN is updated
every 250 ms.