IB-23C650
SETUP
Table 9. Ramp/Soak Profile Setup Menu
Middle
Display
Bottom
Display
Entry Description
**MENU**
None.
REPEAT NO
YES
= Stops ramp/soak cycle after last segment
= Repeats ramp/soak cycle after last segment
HYST xxxx 0 to 30000
Value of hysteresis band for guaranteed soaks.
HYST xxxx 0 to 30000
Value of hysteresis band for guaranteed ramps.
IS OFF
or
IS ON
Note: If
SCRL
is pressed when ramp/soak is
on, message ‘RAMPSOAK RD ONLY’ is
displayed for one second, to indicate
ramp/soak is on and setup therefore is read
only. To make changes to the setup, turn off
ramp/soak in Displays. Any change to setup
will cause profile to reset. If no change is
made, ramp/soak can be turned back on in
Displays, and will continue from stopping point.
UNIT TIM MINUTES
or
HOURS
Time base for all segments used in profile
SEGMENTS xx 0 to 10
Number of segments to be used in profile. If
data is not entered for all segments, profile will
use whatever values are in unconfigured
segments.
SETUP None.
95