IB-23C650
SETUP
Table 1. Base Configuration
Step Step Description
Top
Display
4.1.2.1
Input 2 Calibration Correction.
UP
or
DN
sets correction temperature.
SCRL
advances to Step 5.
I2 TEMP=
5
Output Type.
UP
or
DN
selects output type.
SCRL
advances to Step 5.1.
OUTPUT
5.1
Control Action.
UP
or
DN
selects control action.
SCRL
advances to:
Step 5.2 if output type is CUR PROP,
Step 5.3 if output type is HC/CR or HC/CC,
Step 5.4 if output type is HC/RR,
Step 5.5 if output type is POS PROP, or
Step 6 (Hold Pwr Up Msg) otherwise.
CONTROL
5.2
Milliamp Output Action.
UP
or
DN
selects mA output action.
SCRL
advances to Step 6 (Hold Pwr Up Msg).
MA. OUTP
5.3
Heat Band Output Action.
UP
or
DN
selects heat band output action.
SCRL
advances to Step 5.4.
HEAT OUT