8.6 Single Station Override Control
With Single Station Override Control, two standard
PID control loops function as two interdependent
variables, primary and limiting, to control a single
final element (e.g., valve). Neither variable may
exceed a safe limit. This control strategy is imple-
mented with the controller default settings and the
h.LiM or L.LiM (high or low limiting) control
schemes. The limiting control schemes are de-
faulted to use a value entered into cn.1-b1 parame-
ter as the second loop setpoint.
The primary loop of this control strategy is always
in control unless the output tries to exceed the high
(or low) limit imposed by the limiting loop. As a
high limit controller, the lowest output value is se-
lected to drive the final element via AO1. As a low
limit (high override) controller, the highest output is
selected to drive the final control element via AO1.
A typical high limit controller process application is
illustrated in Figure 8-12. In this application the
valve is normally adjusted in response to primary
variable (flow) disturbances unless the limiting vari-
able (pressure) loop has the highest output. When
this happens, the valve is closed to reduce pres-
sure. Pressure is the limiting variable because it is
the more critical value.
Figure 8-12. Single Station Override
Control Application
The signal connector is illustrated in Figure 8-13
and the connector pin assignment descriptions are
provided in the sections that follow. These sec-
tions also contain the applicable display prompts
that may require configuration changes.
Figure 8-13. Single Station Override
Control Signals
8.6.1 AI1 - Primary PV Input
This is the primary loop analog input signal value
that is compared to the primary loop setpoint to
determine the required primary output. The pri-
mary output is used as the 4-20 mA drive signal for
the final control element if the selector determines
the primary loop should have process control.
Applicable parameters that may require configura-
tion changes:
Section 5.2, conF-Ai.1-(SPan, ZEro, SQrt, bASE,
dFLt).
For PV alarms:
Section 7.7, conF-cn.1-(AiX, PL1, PL2, Adb).
8.6.2 AI2 - Limiting PV Input
This is the limiting loop analog input signal value
that is compared to the limiting loop setpoint. The
output drives the high/low limiter, which affects the
primary output 4-20 mA final control element sig-
nal.
Applicable parameters that may require configura-
tion changes:
Section 5.2, conF-Ai.2-(SPan, ZEro, SQrt, bASE,
dFLt).
8.6.3 DO1 - Primary PV High Alarm
Contact Out
D01 is closed (on) when the primary process vari-
able value is not within the loop 1 (cn.1) process
alarm limit 1 (PL1) setting.
Section 8. Eight Control Strategies 53SL6000 Instruction Manual
8-11