Table 5-3. Input Type Prompts
(conF Menu
Ai.3, Ai.4 Modules)
Prompt Description See
Table
dtot
Delta Pulse Totalize
r (pulse input,
incremental sum) 0-100 kHz
5-7
Table 5-4. Volt/Millivolt Input Types
(conF Menu
Ai.3, Ai.4 Modules)
Prompt Description Dft
tYPE
Make prompt selection
from Table
5-3. Applicable types are:
0-5V, 1-5V, 0-80
.
1-5V
SPAn
ZEro
Engineering Span, Engineering Zero
These values set the engineering
unit representation of the input
signal over the input range.
Ai
=
SPAn
input
%
100
+
ZEro
100.0
0.0
dFLt
Digital Filter
Specifies the time constant in
seconds for a first order filter
through which the input is
processed. The filter dampens the
higher frequency signal
components usually associated with
noise. Selections:
nonE 4.2 75.0 1200
0.3 9.0 150.0 2400
0.6 18.6 300.0
1.8 37.2 600
nonE
SQrt
Square Root Signal
Speciifies whether the analog input
signal requires square root
characterization (as would be the
case for a differential pressure
transducer across an orifice plate),
or linear interpretation. Selections:
Lin:
Linear interpretation.
SQrt:
Square root characterization.
(For SQrt selection, the value
of Ai is forced to 0.0 at low
input signal levels [<6.25%] to
prevent large signal
oscillations.)
Lin
Table 5-5. Thermocouple Types
(conF Menu
Ai.3, Ai.4 Modules)
Prompt Description Dft
tYPE
Make prompt selection
from Table
5-3. Applicable types are:
J.tc S.tc V.tc \S.tc
K.tc b.tc F.tc PL.tc
t.tc n.tc G.tc
E.tc c.tc d.tc
r.tc L.tc \E.tc
1-5V
dFLt
Digital Filter
Specifies the time constant in
seconds for a first order filter
through which the input is
processed. The filter dampens the
higher frequency signal
components usually associated with
noise. Selections:
nonE 4.2 75.0 1200
0.3 9.0 150.0 2400
0.6 18.6 300.0
1.8 37.2 600
nonE
dEG
Temperature Scale
Input selections are as follows:
c:
Celsius scale.
F:
Fahrenheit scale.
c
Table 5-6. RTD Types
(conF Menu
Ai.3, Ai.4 Modules)
Prompt Description Dft
tYPE
Make prompt selection
from Table
5-3. Applicable types are:
Pt.85 53.c
PT.91 100.c
Pt.92 100.n
10.c 120.n
1-5V
dFLt
Digital Filter
Specifies the time constant in
seconds for a first order filter
through which the input is
processed. The filter dampens the
higher frequency signal
components usually associated with
noise. Selections:
nonE 4.2 75.0 1200
0.3 9.0 150.0 2400
0.6 18.6 300.0
1.8 37.2 600
nonE
dEG
Temperature Scale
Input selections are as follows:
c:
Celsius scale.
F:
Fahrenheit scale.
c
rtd
RTD Termination
Input selections are as follows:
3.trM:
3 wire.
4.trM:
4 wire.
3.trM
Section 5. Inputs/Outputs (I/O) 53SL6000 Instruction Manual
5-3
Seitenansicht 46