Seitenansicht 34
Figure 3-9. Editing a tAG
3.6 Entering a Pass-Key
In engineering mode, access to the ProG and conF
menus can be selectively restricted, as each menu
has its own pass-key capabilities. A pass-key is a
four digit number that must be entered when a
menu is selected; otherwise, access to module
prompts in that menu are prohibited. Figure 3-10
illustrates the key display that appears if a menu is
pass-key protected.
Figure 3-10. KEY? Prompt
The correct pass-key must be entered in the red
dro with the following procedure:
1.
Press the scroll forward pb until the desired
number for the first digit appears (assumes
first digit is not a zero).
2.
Press the position select right pb; the second
zero starts blinking.
3.
Repeat steps 1 and 2 to enter all four pass-key
digits.
4.
Press the enter pb; if the pass-key is correct
engineer mode functions are permitted for that
menu.
NOTE:
If the pass-key can not be recalled, then
the database must be defaulted using the
procedure described in Section B.5.
3.6.1 Configuring a Pass-Key
To configure a conF (or ProG) pass-key, the follow-
ing steps must be performed:
1.
Enter engineer mode by pressing and holding
the mode pb until a menu prompt appears in
the green dro.
2.
Press the scroll forward pb until conF (ProG)
appears in the green dro.
3.
Press the enter pb to accept the conF (ProG)
menu.
4.
If KEY does not appear in the yellow dro, press
the scroll forward pb until it does.
5.
Press the enter pb to select the KEY prompt.
cKEY (PKEY) appears in the green dro.
It is assumed the pass-key was never config-
ured before and that four zeros appear in the
red dro:
6.
Press the enter pb; the leftmost number (zero)
in the red dro blinks.
7.
Press the scroll forward pb until the desired
number appears (assumes zero will be
changed to a different number).
8.
Press the shift right pb; the next zero starts
blinking.
9.
Repeat steps 7 and 8 until all four pass-key
digits are entered.
10.
Press the enter pb to enter the pass-key.
11.
Press the mode pb to exit engineer mode.
3.7 Offline Display Pattern
The controller offline state is indicated by four acti-
vated double LED markers along the green vertical
bar as shown in Figure 3-11. The remainder of the
vertical bar is dark.
Events that can cause the controller to be offline
are as follows:
If a ProG menu parameter is altered in engi-
neer mode , it causes the controller to immedi-
ately go offline,
53SL6000 Instruction Manual Section 3. Display Panel
3-8
Seitenansicht 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 137 138

Kommentare zu diesen Handbüchern

Keine Kommentare

Mitsubishi MXZ-4A80VA Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Split-System-Klimaanlagen Mitsubishi MXZ-4A80VA.
Wir stellen 1 PDF-Handbücher Mitsubishi MXZ-4A80VA zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Installationshandbuch