Table 3-3. oPEr Menu Selections
Prompt Description Dft
Adb
Alarm Deadband
Specifies the hystersis (gap)
between alarm trigger and reset.
This value is used to eliminate
repetitive alarm triggering when
the process is fluctuating about a
process limit. This value should be
set slightly larger then the peak-to-
peak fluctuations (noise) which are
normally present in the process
variable signal. (It is enabled with
conF-oPr-ALM.E.)
2.000
Pb
Proportional Band (see Section 8.2)
Specifies the percent of process
deviation from setpoint over the
control range (conF-cn.1[cn.2]-ir)
required to generate a full scale
output signal. For a detailed
discussion on control and tuning,
see Section 9. Values should be
limited between 2 to 1000%. (It is
enabled with conF-oPr-Pid.E.)
100.0
tr
Reset Time (see Section 8.3)
Specifies the time in minutes
required for additional corrective
response (integral action). For a
detailed discussion on control and
tuning, see Section 9. Values
should be limited between 0.02
and 200 minutes /repeat. A value
of 0.0 turns integral action off.
(It is enabled with conF-oPr-Pid.E.)
0.0
td
Derivative Time (see Section 8.4)
Specifies the time in minutes that
control response is advanced over
proportional only action. For a
detailed discussion on control and
tuning, see Section 9. Values
should be limited between 0.01 to 8
minutes. A value of 0.0 turns
derivative action off. (It is enabled
with conF-oPr-Pid.E.)
0.0
Mr
Manual reset
This value determines the position
of the output element (e.g., valve)
when the controller is in automatic
mode and the error is zero. It is only
in effect when tr is zero. (It is
enabled with conF-oPr-Pid.E.)
50.0
oh
Output High Limit
Specifies in percent the maximum
allowable control output during
automatic operation. This limit also
affects outputs during manual
operations when conF-cn.1(cn.2)-
hML is turned on. (It is enabled with
conF-oPr-hLc.E.)
0.0
Table 3-3. oPEr Menu Selections
Prompt Description Dft
oL
Output Low Limit
Specifies in percent the minimum
allowable control output during
automatic operation. This limit also
affects outputs during manual
operations when conF-cn.1(cn.2)-
hML is turned on. (It is enabled with
conF-oPr-hLc.E.)
0.0
cZ
Control Zone
Specifies in engineering units an
area around the setpoint where
the process variable is considered
to be at setpoint (no error). When
the process variable is within this
area, the control output is held
steady at the integrator value as
determined by tr and Mr. Control
Zone is used to reduce valve wear
where process dynamics cause
output oscillations (hunting) when
the process is near its setpoint. (It is
enabled with conF-oPr-hLc.E.)
cZ
cZ
0.0
EZ?
Execute Easy-Tune
Causes Easy-Tune to start
execution. During execution, the
Easy-Tune LED flashes and tunE
appears in the green dro. Upon
successful completion, the Easy-
Tune LED stops flashing and the
green dro no longer displays the
tunE mnemonic. If an error or
warning condition occurs during
execution, the Easy-Tune LED
changes to a steady-state-on
condition and a mnemonic is
displayed in the green dro that
identifies the error or warning.
Pressing the mode/select push
button clears the display. After
taking the appropriate corrective
action(s), Easy-Tune can be
restarted by selecting YeS at the
run? prompt in the EZ menu. (It is
enabled with conF-oPr-EZ.E.)
no
EPb
Easy-Tune Proportional Band
Resultant %PB value calculated by
Easy-Tune. (It is enabled with
conF-oPr-EZ.E.)
0.0
53SL6000 Instruction Manual Section 3. Display Panel
3-10