Micromod Micro-DCI: 53SL5100B Single Loop Controller Bedienungsanleitung Seite 110

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 115
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 109
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
2 PA1n: high when PV> PL1
PA2n: not affected
3 PA1n: not affected
PA2n: low when PV< PL1
low when PV< PL1
ev > PL1
ev < PL2
4 PA1n: high when PV> PL1
PA2n: hi-hi when PV> PL2
5 PA1n:
PA2n: lo-lo when PV< PL2
6 PA1: Hi-Dev when D
PA2: Lo-Dev when D
Alarm Examples:
B335 PV PL1
(C103)
PL2
(C104)
Alarm Setpoint Notes
0 >60 60 HIGH a > 60 = HIGH alarm Al rm Llimit 1 is set for 60: PV
0 <40 40 LOW a = LOW alarm Al rm Limit 2 is set for 40: PV < 40
2 >60 60 HIGH Limit 1 is set for 60: PV > 60 = HIGH alarm Alarm
2 <40 40 N/A Alarm Limit 2 is set for 40: PV < 40 = no alarm
3 >60 60 N/A Alarm Limit 1 is set for 60: PV > 60 = no alarm
3 <40 40 LOW
Low Alarm Limit 2 is set for 40: PV < 40 = LOW
alarm
4 >60 60 HIGH Alarm Limit 1 is set for 60: PV > 60 = HIGH alarm
4 <70 70 HI- HI Alarm Limit 2 is set for 70: PV > 70 = HI-HI alarm
5 >40 40 LOW Alarm Limit 1 is set for 40: PV < 40 = LOW alarm
5 <30 30 LO-LO imit 2 is set for 30: PV < 30 = LO-LO alarm Alarm L
6 >50 10 HI-DEV 40 Alarm Limit 1 is set for 40: PV < 40 = HI-DEV alarm
6 <30 -10 LO-DEV 40
larm
Alarm Limit 2 is set for 30: PV < 30 = LO-DEV
a
Analog Output
(Display Only)
ANO0 C00 0
The v
output to be generated by hardware (e.g., 100 % output =
20 m
0
alue in this datapoint represents the percent of
A).
Process Variable
PV C100 0
lgor
This is the actual PV variable of the controller PID
a ithm. It is obtained from ANI0.
S oint SP C1
0
his i ed
decrease pushbuttons or from
etp 01 T
from the setpoint increase/
s the actual setpoint of the PID algorithm obtain
Remote Setpoint (RSP).
Output
OUT C102 0
hm; otherwise, it is the value determined by
When in Auto, this is the actual result of the controller
PID algorit
the output pushbuttons. it is transferred to ANO0.
Alarm Limit 1
PL1 C103 100
ring units at which This parameter is the point in enginee
the upper alarm is triggered.
Alarm Limit 2
PL2 C104 0
.
This parameter is the point in engineering units at which
the lower alarm is triggered
Alarm Dead Band
ea
ADB C105 2
This parameter sets the activation/deactivation gap for
the alarm. This value in engineering units defines an ar
of hysteresis at the alarm point.
Proportional Band
ional action. It modifies the
PB C106 100
This parameter is the percent of error required to move
the output full scale for proport
104
Seitenansicht 109

Kommentare zu diesen Handbüchern

Keine Kommentare