ALARM TYPE:
The AIX parameter (B335) defines the alarm action interpretation of the two alarm limits.
0 - PA1HIGH (PV > PL1)
PA2LOW (PV < PL2)
1 - None
2 - PA1HIGH (PV > PL1)
PA2not effected
3 - PA1not effected
PA2LOW (PV < PL1)
4 - PA1HIGH (PV > PL1)
PA2HI-HI (PV > PL2)
5 - PA1LOW (PV < PL1)
PA2LO-LO (PV < PL2)
6 - PA1 HI-DEV (DEV > PL1)
PA2LO-DEV (DEV < PL2)
TREND RATE:
This parameter(B336) defines the sampling rate of the PV trend displayed in seconds. The legal
values are 0, 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 seconds. If any other value is set it will be
reduced to one of these values.
TREND MODE:
This parameter(B337) specifies the mode of the PV trend.
0 - use instantaneous samples
1 - average of 1 second samples
2 - maximum of 1 second samples
3 - minimum of 1 second samples
DISPLAY MODE:
This parameter(B339) controls the type of point display which will be used with this CON module.
0 - standard PID
1 - Indicator
2 - Manual loader
3 - Ratio Controller
4 - A/M station
5 - Ratio A/M station
MODULAR CONTROLLER QUICK START
3-37