The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L419=1.
•
The 53MC5000 is set to accept a linear PV signal. If square root extraction is
required, set L443=1.
2. Enable Output Tracking by setting L119=1.
3. The 53MC5000 will track AI3 only if DI0 is open (0 state).
MODULAR CONTROLLER QUICK START
4-6